      "slug": "kva-to-amps-calculator",
      "title": "kVA to Amps, Breaker & Feeder Calculator (3-Phase / 1-Phase)",
      "url": "https://kvacalc.com/tools/kva-to-amps-calculator",
      "formulaSummary": "I_3Ø = (kVA × 1000) / (1.732 × V_LL)  |  I_1Ø = (kVA × 1000) / V_LN  |  OCPD = 1.25 × FLA",
      "referenceRows": [
        {
          "tier": "45 kVA Dry-Type 3Ø",
          "spec": "480 V Primary -> 208Y/120 V Secondary",
          "throughput": "54.1 A Pri / 124.9 A Sec",
          "monthlyEst": "70 A Pri / 175 A Sec OCPD"
        },
        {
          "tier": "75 kVA Dry-Type 3Ø",
          "spec": "480 V Primary -> 208Y/120 V Secondary",
          "throughput": "90.2 A Pri / 208.2 A Sec",
          "monthlyEst": "125 A Pri / 300 A Sec OCPD"
        },
        {
          "tier": "250 kVA IEC Cast-Resin 3Ø",
          "spec": "20 kV Primary -> 400Y/230 V Secondary",
          "throughput": "7.2 A Pri / 360.8 A Sec",
          "monthlyEst": "400 A / 450 A LV ACB"
        },
        {
          "tier": "500 kVA Substation 3Ø",
          "spec": "13.8 kV Primary -> 480Y/277 V Secondary",
          "throughput": "20.9 A Pri / 601.4 A Sec",
          "monthlyEst": "800 A LV Main Breaker"
        }
      ]
    },
    {
      "slug": "three-phase-voltage-drop-calculator",
      "title": "Three-Phase & Single-Phase Voltage Drop Calculator (NEC / IEC)",
      "url": "https://kvacalc.com/tools/three-phase-voltage-drop-calculator",
      "formulaSummary": "Vd = K × I × L_km × (R_75C·cosφ + X_L·sinφ)  [K = √3 for 3Ø, K = 2 for 1Ø]",
      "referenceRows": [
        {
          "tier": "NEC 210.19 / NOM-001 Branch",
          "spec": "Individual Feeder or Branch Run",
          "throughput": "Max Recommended <= 3.0 %",
          "monthlyEst": "14.4 V max @ 480V"
        },
        {
          "tier": "NEC 215.2 Total System",
          "spec": "Feeder + Branch Combined",
          "throughput": "Max Cumulative <= 5.0 %",
          "monthlyEst": "24.0 V max @ 480V"
        },
        {
          "tier": "IEC 60364-5-52 Lighting",
          "spec": "Public LV Supply Lighting",
          "throughput": "Max Allowed <= 3.0 %",
          "monthlyEst": "12.0 V max @ 400V"
        },
        {
          "tier": "NEC 647.4 Sensitive Equipment",
          "spec": "60/120V Technical Power",
          "throughput": "Strict Mandatory <= 1.5 %",
          "monthlyEst": "2.0 % Combined Max"
        }
      ]
    },
    {
      "slug": "awg-to-mm2-ampacity-converter",
      "title": "AWG to mm² Cross-Section & NEC 310.16 Ampacity Derating Calculator",
      "url": "https://kvacalc.com/tools/awg-to-mm2-ampacity-converter",
      "formulaSummary": "I_derated = I_base(Table 310.16) × K_temp(310.15(B)(1)) × K_bundle(310.15(C)(1))",
      "referenceRows": [
        {
          "tier": "12 AWG <-> 4 mm² IEC",
          "spec": "Exact 3.31 mm² (6.53 kcmil)",
          "throughput": "20 A (60°C) / 25 A (75°C) / 30 A (90°C)",
          "monthlyEst": "NEC 240.4(D) Max 20 A OCPD"
        },
        {
          "tier": "10 AWG <-> 6 mm² IEC",
          "spec": "Exact 5.26 mm² (10.38 kcmil)",
          "throughput": "30 A (60°C) / 35 A (75°C) / 40 A (90°C)",
          "monthlyEst": "NEC 240.4(D) Max 30 A OCPD"
        },
        {
          "tier": "6 AWG <-> 16 mm² IEC",
          "spec": "Exact 13.30 mm² (26.24 kcmil)",
          "throughput": "55 A (60°C) / 65 A (75°C) / 75 A (90°C)",
          "monthlyEst": "65 A @ 75°C Breaker Lugs"
        },
        {
          "tier": "1/0 AWG <-> 50 mm² IEC",
          "spec": "Exact 53.49 mm² (105.6 kcmil)",
          "throughput": "125 A (60°C) / 150 A (75°C) / 170 A (90°C)",
          "monthlyEst": "150 A @ 75°C Breaker Lugs"
        }
      ]
    },
    {
      "slug": "plc-4-20ma-scaling-calculator",
      "title": "PLC 4–20 mA / 0–10 V Analog Scaling & NAMUR NE43 Calculator",
      "url": "https://kvacalc.com/tools/plc-4-20ma-scaling-calculator",
      "formulaSummary": "EU = LRV + ((I_mA − 4.0) / 16.0) × (URV − LRV)  |  Raw = Raw_min + Span × (Raw_max − Raw_min)",
      "referenceRows": [
        {
          "tier": "NAMUR NE43 Low Fault",
          "spec": "Signal <= 3.60 mA",
          "throughput": "Raw < -691 (27648 scale)",
          "monthlyEst": "Wire Break / Burnout Low"
        },
        {
          "tier": "0% Span (LRV)",
          "spec": "4.00 mA / 1.00 V @ 250 Ω",
          "throughput": "0 Counts (or 4000 Prop.)",
          "monthlyEst": "Engineering LRV"
        },
        {
          "tier": "50% Mid-Span Check",
          "spec": "12.00 mA / 3.00 V @ 250 Ω",
          "throughput": "13,824 Counts (27648 scale)",
          "monthlyEst": "Midpoint Calibration"
        },
        {
          "tier": "100% Span (URV) & High Fault",
          "spec": "20.00 mA (Fault >= 21.0 mA)",
          "throughput": "27,648 Counts (29,376 @ 21mA)",
          "monthlyEst": "URV / High Burnout"
        }
      ]
    },
    {
      "slug": "solar-string-voc-mppt-calculator",
      "title": "Solar PV String Sizing, Cold-Weather Voc & MPPT Window Calculator",
      "url": "https://kvacalc.com/tools/solar-string-voc-mppt-calculator",
      "formulaSummary": "Voc_max = Voc_STC × [1 + (β_Voc / 100) × (T_min − 25)]  |  N_max = floor(V_dc_max / Voc_max)",
      "referenceRows": [
        {
          "tier": "NEC Dwelling Rooftop",
          "spec": "Max System Voltage 600 VDC",
          "throughput": "Typically 11–14 Modules / String",
          "monthlyEst": "NEC 690.7(C) Limit"
        },
        {
          "tier": "Commercial 3-Phase PV",
          "spec": "Max System Voltage 1000–1100 VDC",
          "throughput": "Typically 17–20 Modules / String",
          "monthlyEst": "IEC 62548 / NEC C&I"
        },
        {
          "tier": "Utility Central / String",
          "spec": "Max System Voltage 1500 VDC",
          "throughput": "Typically 26–30 Modules / String",
          "monthlyEst": "Utility Tracker Standard"
        },
        {
          "tier": "Cold Surge @ -20°C (ΔT=-45°C)",
          "spec": "β_Voc = -0.26 %/°C",
          "throughput": "Voc Multiplier = 1.117× STC",
          "monthlyEst": "+11.7% Open-Circuit Boost"
        }
      ]
    },
    {
      "slug": "nec-conduit-fill-calculator",
      "title": "NEC Chapter 9 Conduit Fill & Cable Pull Jam Ratio Calculator",
      "url": "https://kvacalc.com/tools/nec-conduit-fill-calculator",
      "formulaSummary": "Fill % = (N × A_wire / A_conduit) × 100  [Max: 53% (1 wire), 31% (2 wires), 40% (3+ wires)]",
      "referenceRows": [
        {
          "tier": "1 Conductor in Raceway",
          "spec": "NEC Chapter 9 Table 1",
          "throughput": "Max Allowed Fill <= 53 %",
          "monthlyEst": "Single Cable Pull"
        },
        {
          "tier": "2 Conductors in Raceway",
          "spec": "NEC Chapter 9 Table 1",
          "throughput": "Max Allowed Fill <= 31 %",
          "monthlyEst": "Anti-Oval Wedging Rule"
        },
        {
          "tier": "3 or More Conductors",
          "spec": "NEC Chapter 9 Table 1 ( & NBR 5410 )",
          "throughput": "Max Allowed Fill <= 40 %",
          "monthlyEst": "Standard Feeder / Branch"
        },
        {
          "tier": "Conduit Nipple <= 24 in (600 mm)",
          "spec": "NEC Chapter 9 Note 4",
          "throughput": "Permitted Fill <= 60 %",
          "monthlyEst": "No Bundling Derating"
        }
      ]
    }
  ]
}