Industrial Electrical, kVA, Motor & Cable Sizing Calculators

11 deterministic browser-based electrical engineering workbenches for transformers, NEC 430 motors, standby generators, voltage drop, fault kAIC, UPS backup, and PLC loops.

Quick Load:
Std Transformer kVA:
AC System Phase Configuration
kVA
A
kW
cos φ
Full-Load Current (FLA)
Calculated FLA + Preliminary NEC Sizing
120.28 A
120.28 A FLA | Prelim. 175 A OCPD | 2/0 AWG (IEC >= 70 mm²)
Prelim. OCPD Breaker
175 A
Real / Reactive Power
85.0 kW (100.0 kVA)
Prelim. 75°C Cu Feeder
2/0 AWG (IEC >= 70 mm²)
FLA (120.28 A) is exact steady-state math. Breaker (175 A) & feeder (2/0 AWG (IEC >= 70 mm²)) are preliminary NEC 215.2 / 215.3 (125% Continuous Feeder) screening — verify ambient/bundling derating & NEC 450.3 coordination.
System VoltageFull-Load AmpsPrelim. OCPDPrelim. 75°C Cu
208 V 3Ø (Wye)277.57 A350 A500 kcmil (IEC >= 300 mm²)
400 V 3Ø (IEC/VDE)144.34 A200 A3/0 AWG (IEC >= 95 mm²)
480 V 3Ø (NEC)120.28 A175 A2/0 AWG (IEC >= 70 mm²)
600 V 3Ø (CSA)96.23 A125 A1 AWG (IEC >= 50 mm²)
Formula
SkVA=3⋅VLL⋅I1000S_{\text{kVA}} = \frac{\sqrt{3} \cdot V_{LL} \cdot I}{1000}PkW=SkVA⋅cosφP_{\text{kW}} = S_{\text{kVA}} \cdot \cos\varphiQkVAR=SkVA2−PkW2Q_{\text{kVAR}} = \sqrt{S_{\text{kVA}}^{2} - P_{\text{kW}}^{2}}
Reviewed against NFPA 70 (NEC 2023) & IEC 60364 • Verified 2026-11-18 Preliminary engineering estimation only; final stamped drawings and protective device coordination must be verified by a licensed Professional Engineer (PE) and local AHJ. View Full 11-Tool Standards & Golden Test Matrix →

Power & Protection (6)

Wiring, Backup & PLC (5)

Standard kVA to Amps Quick-Reference Matrix (1 kVA – 1,000 kVA)

Direct full-load current (FLA) lookup across common NEMA, IEC, and industrial distribution voltages. 1 kVA unit benchmarks: 120V 1Ø = 8.33 A, 240V 1Ø = 4.17 A, 208V 3Ø = 2.78 A, 240V 3Ø = 2.41 A, 400V 3Ø = 1.44 A, and 480V 3Ø = 1.20 A.

Transformer kVA 120V 1Ø 240V 1Ø 208V 3Ø 240V 3Ø 400V 3Ø 480V 3Ø
1 kVA 8.33 A 4.17 A 2.78 A 2.41 A 1.44 A 1.20 A
5 kVA 41.67 A 20.83 A 13.88 A 12.03 A 7.22 A 6.01 A
10 kVA 83.33 A 41.67 A 27.76 A 24.06 A 14.43 A 12.03 A
15 kVA 125.00 A 62.50 A 41.64 A 36.08 A 21.65 A 18.04 A
25 kVA 208.33 A 104.17 A 69.39 A 60.14 A 36.08 A 30.07 A
30 kVA 250.00 A 125.00 A 83.27 A 72.17 A 43.30 A 36.08 A
45 kVA 375.00 A 187.50 A 124.91 A 108.25 A 64.95 A 54.13 A
50 kVA 416.67 A 208.33 A 138.79 A 120.28 A 72.17 A 60.14 A
75 kVA 625.00 A 312.50 A 208.18 A 180.42 A 108.25 A 90.21 A
100 kVA 833.33 A 416.67 A 277.57 A 240.56 A 144.34 A 120.28 A
112.5 kVA 937.50 A 468.75 A 312.27 A 270.63 A 162.38 A 135.32 A
150 kVA 1250.00 A 625.00 A 416.36 A 360.84 A 216.51 A 180.42 A
225 kVA 1875.00 A 937.50 A 624.54 A 541.27 A 324.76 A 270.63 A
300 kVA 2500.00 A 1250.00 A 832.72 A 721.69 A 433.01 A 360.84 A
500 kVA 4166.67 A 2083.33 A 1387.86 A 1202.81 A 721.69 A 601.41 A
750 kVA 6250.00 A 3125.00 A 2081.79 A 1804.22 A 1082.53 A 902.11 A
1000 kVA 8333.33 A 4166.67 A 2775.72 A 2405.63 A 1443.38 A 1202.81 A

Deterministic Field Engineering Suite — NEC 2023, IEC 60364 & ISO 8528

kVACalc organizes eleven specialized power distribution, motor protection, cable ampacity, backup power, solar PV string, and PLC 4–20 mA scaling workbenches into a single offline-capable progressive web app. Use the omnidirectional quick-converter above to solve kVA, Amps, or kW in real time, then hand off exact load currents directly into voltage drop, conduit fill, or capacitor bank sizing.

Every workbench encodes URL query parameters for one-click engineering review, generates single-page print/PDF calculation sheets with live substituted steps, and executes 100% locally in your browser without uploading substation schedules.

Frequently Asked Questions

How many amps is 1 kVA across standard single-phase and three-phase voltages?

At 1 kVA of apparent power: 120V single-phase = 8.33 A, 240V single-phase = 4.17 A, 208V three-phase = 2.78 A, 240V three-phase = 2.41 A, 400V three-phase (IEC) = 1.44 A, and 480V three-phase (NEC) = 1.20 A.

Which kVACalc workbench should I use for transformer vs motor vs generator sizing?

Use the kVA to Amps Calculator for dry-type or pad-mounted transformers (NEC 450.3), the kW / Amps / HP Motor Calculator for induction motors (NEC Table 430.250 FLC & 430.52 breakers), and the Generator Sizing Calculator when accounting for 1.5×–6× locked-rotor motor starting surge and altitude derating.

Can electricians use kVACalc offline inside mechanical rooms and substations?

Yes. kVACalc includes a Web App Manifest and Service Worker that caches all 11 calculators locally on your phone or laptop so calculations, presets, and recent history work without cellular reception.

How do I share or print an exact calculation for an engineering submittal?

Every input change updates shareable URL query parameters (?kva=100&voltage=480&phase=3). Click Copy Share Link to send the exact state to a colleague, or click Print / PDF for a clean single-page calculation sheet.

Full-Load Current (FLA) 120.28 A