kVA to Amps, Breaker & Feeder Calculator (3-Phase / 1-Phase)

Compute full-load current (FLA), continuous 125% OCPD breaker sizing, active kW, reactive kVAR, and 75°C copper cable sizes across 120V to 13.8kV systems.

Examples:
Std Transformer kVA:
AC System Phase Configuration
kVA
A
kW
cos φ
Feeder Conductor Metal (75°C)
Full-Load Current (FLA)
Calculated FLA + Preliminary NEC Sizing
90.21 A
90.21 A FLA | Prelim. 125 A OCPD | 2 AWG (IEC >= 35 mm²)
Prelim. OCPD Breaker
125 A
Real / Reactive Power
63.8 kW / 39.5 kVAR
Prelim. 75°C Cu Feeder
2 AWG (IEC >= 35 mm²)
FLA (90.21 A) is exact steady-state math. Breaker (125 A) & feeder (2 AWG (IEC >= 35 mm²)) are preliminary NEC 215.2 / 215.3 (125% Continuous Feeder) screening — verify ambient/bundling derating & NEC 450.3 coordination.
AC Power Triangle (S / P / Q)
P = 63.8 kW Q = 39.5 kVAR S = 75.0 kVA PF 0.85 (φ = 31.8°)
PF 0.85 < 0.95 — Add 18.6 kVAR bank for 0.95 PF Size kVAR Bank ->
System VoltageFull-Load AmpsPrelim. OCPDPrelim. 75°C Cu
208 V 3Ø (Wye)208.18 A300 A350 kcmil (IEC >= 185 mm²)
400 V 3Ø (IEC/VDE)108.25 A150 A1/0 AWG (IEC >= 70 mm²)
480 V 3Ø (NEC)90.21 A125 A2 AWG (IEC >= 35 mm²)
600 V 3Ø (CSA)72.17 A100 A3 AWG (IEC >= 35 mm²)
How It Was Calculated (Live Substituted Steps)
  1. 1. Full-Load Current (I_FLA — Exact) 90.21 A
    I=1000⋅SkVA3⋅VLLI = \tfrac{1000 \cdot S_{\text{kVA}}}{\sqrt{3} \cdot V_{LL}} → (75.00 × 1000) / (1.732 × 480)
  2. 2. Active & Reactive Power Split (P / Q — Exact) 63.75 kW / 39.51 kVAR
    P=S⋅cosφ|Q=S2−P2P = S \cdot \cos\varphi \;\mid\; Q = \sqrt{S^{2} - P^{2}} → 75.00 × 0.85 = 63.75 kW
  3. 3. Preliminary OCPD & 75°C Feeder (NEC 215.2 / 215.3 (125% Continuous Feeder)) 125 A Breaker | 2 AWG (IEC >= 35 mm²)
    IOCPD=IFLA⋅KNECI_{\text{OCPD}} = I_{\text{FLA}} \cdot K_{\text{NEC}} → 90.21 A × 1.25 = 112.76 A
Formula
I3ϕ=1000⋅SkVA3⋅VLLI_{3\phi} = \frac{1000 \cdot S_{\text{kVA}}}{\sqrt{3} \cdot V_{LL}}I1ϕ=1000⋅SkVAVI_{1\phi} = \frac{1000 \cdot S_{\text{kVA}}}{V}SkVA=PkWcosφS_{\text{kVA}} = \frac{P_{\text{kW}}}{\cos\varphi}IOCPD=KNEC⋅IFLAI_{\text{OCPD}} = K_{\text{NEC}} \cdot I_{\text{FLA}}
Reviewed against NFPA 70 (NEC 2023) & IEC 60364 • Verified 2026-11-18 Preliminary engineering estimation only; final stamped drawings and protective device coordination must be verified by a licensed Professional Engineer (PE) and local AHJ. View Full 11-Tool Standards & Golden Test Matrix →

How to Convert Three-Phase & Single-Phase kVA to Full-Load Amps

Transformers, standby diesel generators, and industrial uninterruptible power supplies (UPS) are rated in kilovolt-amperes (kVA) rather than kilowatts (kW) because internal copper winding losses (I²R) and core heating depend on total apparent current regardless of load power factor. On a single-phase circuit, full-load current equals apparent power in volt-amperes divided by line voltage: I = (kVA × 1000) / V.

On a balanced three-phase distribution bus (such as 208 V commercial wye, 400 V IEC/VDE industrial wye, or 480 V NEC plant switchgear), phase currents are displaced by 120 electrical degrees, introducing the square root of three (√3 ≈ 1.73205) into the denominator: I = (kVA × 1000) / (1.732 × V_LL). For example, a standard 75 kVA dry-type transformer draws 90.21 A on its 480 V primary and 208.18 A on its 208Y/120 V secondary.

NEC 450.3(B) Overcurrent Protection & 75°C Feeder Lug Termination Rules

Under NFPA 70 (NEC Table 450.3(B) for transformers rated 1000 V or less with primary currents of 9 A or more) and continuous feeder rule NEC 215.3, primary overcurrent protective devices (OCPD) and secondary feeder conductors are typically sized at 125% of full-load current. Where 125% of transformer current does not correspond to a standard NEC 240.6(A) circuit breaker or fuse rating, Note 1 to Table 450.3(B) permits rounding up to the next higher standard rating.

Pursuant to NEC 110.14(C)(1), circuit breaker and transformer lugs on equipment rated above 100 A (or marked 75°C) require selecting conductor ampacity from the 75°C column of NEC Table 310.16—even when pulling 90°C THHN/THWN-2 or XHHW-2 wire—unless ambient temperature and conduit fill derating require using the 90°C starting value.

Engineering Scope, Standards Edition & Model Limitations

Calculated FLA + Preliminary NEC Sizing Formula v2.1.0 Reviewed 2026-11-18 View Full 11-Tool Standards & Golden Test Matrix →
Referenced Code Editions & Clauses Edition Applicable Clauses & Engineering Scope
NFPA 70 (NEC) 2023 Edition Art. 215.2, 215.3, 240.4(B)/(D), 240.6(A), Table 310.16, Table 450.3(B), 110.14(C)
IEC 60364-5-52 / IEC 60228 2009 / 2004 Upsized nominal metric cross-sections (mm² >= exact ASTM B258 area)

Mathematical Model Assumptions

  • Balanced sinusoidal steady-state AC load in three-phase (√3 = 1.73205) or single-phase circuits.
  • Base conductor sizing references NEC Table 310.16 75°C column (<=3 current-carrying conductors in raceway at 30°C ambient).
  • Metric conductor labels denote minimum upsized IEC 60228 nominal cross-section (>= exact AWG/kcmil geometric area).

Out-of-Scope Boundaries & Required PE Verification

  • NEC Table 450.3(B) transformer OCPD depends on primary-only vs primary+secondary coordination, >1000V rules (450.3(A)), and supervised location exceptions.
  • Circuits <=100 A or #14–#1 AWG require 60°C ampacity sizing per NEC 110.14(C)(1)(a) unless equipment terminals are listed and marked for 75°C.
  • Does not apply ambient temperature (>30°C), raceway bundling (>3 conductors), harmonic neutral currents, or feeder voltage-drop upsizing automatically.

Reference Benchmark & Formula Specification

Deterministic formula
I3ϕ=1000⋅SkVA3⋅VLLI_{3\phi} = \frac{1000 \cdot S_{\text{kVA}}}{\sqrt{3} \cdot V_{LL}}I1ϕ=1000⋅SkVAVI_{1\phi} = \frac{1000 \cdot S_{\text{kVA}}}{V}SkVA=PkWcosφS_{\text{kVA}} = \frac{P_{\text{kW}}}{\cos\varphi}IOCPD=KNEC⋅IFLAI_{\text{OCPD}} = K_{\text{NEC}} \cdot I_{\text{FLA}}
Architecture / Standard Tier Specification Scope / Operating Range Reference Benchmark
45 kVA Dry-Type 3Ø 480 V Primary -> 208Y/120 V Secondary 54.1 A Pri / 124.9 A Sec 70 A Pri / 175 A Sec OCPD
75 kVA Dry-Type 3Ø 480 V Primary -> 208Y/120 V Secondary 90.2 A Pri / 208.2 A Sec 125 A Pri / 300 A Sec OCPD
250 kVA IEC Cast-Resin 3Ø 20 kV Primary -> 400Y/230 V Secondary 7.2 A Pri / 360.8 A Sec 400 A / 450 A LV ACB
500 kVA Substation 3Ø 13.8 kV Primary -> 480Y/277 V Secondary 20.9 A Pri / 601.4 A Sec 800 A LV Main Breaker

Standard kVA to Amps Quick-Reference Matrix (1 kVA – 1,000 kVA)

Direct full-load current (FLA) lookup across common NEMA, IEC, and industrial distribution voltages. 1 kVA unit benchmarks: 120V 1Ø = 8.33 A, 240V 1Ø = 4.17 A, 208V 3Ø = 2.78 A, 240V 3Ø = 2.41 A, 400V 3Ø = 1.44 A, and 480V 3Ø = 1.20 A.

Transformer kVA 120V 1Ø 240V 1Ø 208V 3Ø 240V 3Ø 400V 3Ø 480V 3Ø
1 kVA 8.33 A 4.17 A 2.78 A 2.41 A 1.44 A 1.20 A
5 kVA 41.67 A 20.83 A 13.88 A 12.03 A 7.22 A 6.01 A
10 kVA 83.33 A 41.67 A 27.76 A 24.06 A 14.43 A 12.03 A
15 kVA 125.00 A 62.50 A 41.64 A 36.08 A 21.65 A 18.04 A
25 kVA 208.33 A 104.17 A 69.39 A 60.14 A 36.08 A 30.07 A
30 kVA 250.00 A 125.00 A 83.27 A 72.17 A 43.30 A 36.08 A
45 kVA 375.00 A 187.50 A 124.91 A 108.25 A 64.95 A 54.13 A
50 kVA 416.67 A 208.33 A 138.79 A 120.28 A 72.17 A 60.14 A
75 kVA 625.00 A 312.50 A 208.18 A 180.42 A 108.25 A 90.21 A
100 kVA 833.33 A 416.67 A 277.57 A 240.56 A 144.34 A 120.28 A
112.5 kVA 937.50 A 468.75 A 312.27 A 270.63 A 162.38 A 135.32 A
150 kVA 1250.00 A 625.00 A 416.36 A 360.84 A 216.51 A 180.42 A
225 kVA 1875.00 A 937.50 A 624.54 A 541.27 A 324.76 A 270.63 A
300 kVA 2500.00 A 1250.00 A 832.72 A 721.69 A 433.01 A 360.84 A
500 kVA 4166.67 A 2083.33 A 1387.86 A 1202.81 A 721.69 A 601.41 A
750 kVA 6250.00 A 3125.00 A 2081.79 A 1804.22 A 1082.53 A 902.11 A
1000 kVA 8333.33 A 4166.67 A 2775.72 A 2405.63 A 1443.38 A 1202.81 A

Frequently Asked Questions

How many amps is 1 kVA at 120V, 240V, 208V, 400V, and 480V?

On single-phase circuits: 1 kVA at 120V = 8.33 A, 1 kVA at 230V = 4.35 A, and 1 kVA at 240V = 4.17 A. On balanced three-phase circuits: 1 kVA at 208V = 2.78 A, 1 kVA at 400V = 1.44 A, 1 kVA at 480V = 1.20 A, and 1 kVA at 600V = 0.96 A. Multiply any transformer kVA rating by these constants for instant full-load amps.

Does power factor (cos φ) change the full-load amps of a kVA rating?

No. Because kVA already represents total apparent power (S = V × I × √3), full-load current depends solely on kVA and system voltage. Power factor determines how much of that kVA converts into usable real power (kW = kVA × cos φ) versus magnetizing reactive power (kVAR).

How many amps is a 75 kVA transformer at 480V and 208V three-phase?

At 480V three-phase, a 75 kVA transformer draws 90.21 A full-load (requiring a 112.8 A -> 125 A primary breaker at 125%). On a 208V three-phase secondary, it delivers 208.18 A full-load (260.2 A at 125%, typically protected at 250 A or 300 A per NEC 240.4(B) / 450.3(B)).

When should I select 100% instead of 125% breaker sizing?

Use 125% for continuous loads operating 3 hours or more (NEC 215.2 / 210.20) and NEC 450.3(B) primary-only transformer protection. Select 100% when evaluating nominal IEC 60076 nameplate current or listed 100%-rated electronic trip switchgear assemblies.

Related Engineering Calculators & Workbenches

Full-Load Current (FLA) 90.21 A
Inputs ↑